Site Accessibility Evaluation

Charlottesville Circuit Court
315 E High St
North Downtown, VA 22902
Inspection Date: 02/01/2024
Inspectors: Brandon Hill
Prepared By
Precision Infrastructure Management
(800) 734 - 8891
www.PrecisionInfrastructureMgmt.com
Report Date: 09/20/2024

Findings

Basement level: Lower Court room

Finding: 1

The door opening contains projections into doorway below 34 inches.

Door openings shall provide a clear width of 32 inches minimum. There shall be no projections into the required clear opening width lower than 34 inches above the finish floor or ground. Projections into the clear opening width between 34 inches and 80 inches above the finish floor or ground shall not exceed 4 inches
Citation:
2010 ADAS Section 404.2.3
Door openings shall provide a clear width of 32 inches (815 mm) minimum. Clear openings of doorways with swinging doors shall be measured between the face of the door and the stop, with the door open 90 degrees. Openings more than 24 inches (610 mm) deep shall provide a clear opening of 36 inches (915 mm) minimum. There shall be no projections into the required clear opening width lower than 34 inches (865 mm) above the finish floor or ground. Projections into the clear opening width between 34 inches (865 mm) and 80 inches (2030 mm) above the finish floor or ground shall not exceed 4 inches (100 mm).

Recommendation:
Relocate elements to provide door clearance.
Barrier Priority:
Important (2): Should be completed as soon as possible. (Includes; Findings that would remove barriers to the greatest number of people to your goods and services)
Finding 849585 Main Photo
Image that depicts the citation requirements of the code or standard
Additional Finding Photos
Finding 849585 Additional Photo

Finding: 2

The force required to operate the door hardware exceeds 5 pounds.

The force required to activate operable parts is 5 pounds maximum.
Citation:
2010 ADAS Section 309.4
Operable parts shall be operable with one hand and shall not require tight grasping, pinching, or twisting of the wrist. The force required to activate operable parts shall be 5 pounds (22.2 N) maximum.

Recommendation:
Adjust or replace push bar.
Barrier Priority:
Important (2): Should be completed as soon as possible. (Includes; Findings that would remove barriers to the greatest number of people to your goods and services)
Finding 849586 Main Photo

Finding: 3

The door exceeds the maximum allowable opening force.

Interior doors shall have a maximum opening force of 5 pounds.

These forces do not apply to the force required to retract latch bolts or disengage other devices that hold the door or gate in a closed position.
Citation:
2010 ADAS Section 404.2.9
Fire doors shall have a minimum opening force allowable by the appropriate administrative authority. The force for pushing or pulling open a door or gate other than fire doors shall be as follows: 1. Interior hinged doors and gates: 5 pounds (22.2 N) maximum. 2. Sliding or folding doors: 5 pounds (22.2 N) maximum. These forces do not apply to the force required to retract latch bolts or disengage other devices that hold the door or gate in a closed position.

Recommendation:
Adjust or replace door closer.
Barrier Priority:
Important (2): Should be completed as soon as possible. (Includes; Findings that would remove barriers to the greatest number of people to your goods and services)
Finding 849587 Main Photo
Image that depicts the citation requirements of the code or standard

Basement level: Jury Chamber

Finding: 4

The paper towel dispenser's operation mechanism is too high off the floor.

Dispensers must have all operable parts a maximum of 48 inches above the floor.
Citation:
2010 ADAS Section 308.2.1
Where a forward reach is unobstructed, the high forward reach shall be 48 inches (1220 mm) maximum and the low forward reach shall be 15 inches (380 mm) minimum above the finish floor or ground.

Recommendation:
Move dispenser to compliant height.
Barrier Priority:
Low (4): Should be completed as soon as possible due to being a technical violation, but may not result in providing greater access to persons with disabilities. (Includes; Findings that are technically violations but provide a moderate to low increase in accessibility compared to the financial impact on the entity)
Finding 849581 Main Photo
Image that depicts the citation requirements of the code or standard

Finding: 5

The element is not accessible because there is not adequate clear floor space for an approach.

The clear floor or ground space shall be 30 inches minimum by 48 inches minimum.
Citation:
2010 ADAS Section 305.3
The clear floor or ground space shall be 30 inches (760 mm) minimum by 48 inches (1220 mm) minimum

Recommendation:
Move pictures; relocate refrigerator to provide clear floor space.
Barrier Priority:
Important (2): Should be completed as soon as possible. (Includes; Findings that would remove barriers to the greatest number of people to your goods and services)
Finding 849582 Main Photo
Image that depicts the citation requirements of the code or standard

Finding: 6

The door exceeds the maximum allowable opening force.

Interior doors shall have a maximum opening force of 5 pounds.

These forces do not apply to the force required to retract latch bolts or disengage other devices that hold the door or gate in a closed position.
Citation:
2010 ADAS Section 404.2.9
Fire doors shall have a minimum opening force allowable by the appropriate administrative authority. The force for pushing or pulling open a door or gate other than fire doors shall be as follows: 1. Interior hinged doors and gates: 5 pounds (22.2 N) maximum. 2. Sliding or folding doors: 5 pounds (22.2 N) maximum. These forces do not apply to the force required to retract latch bolts or disengage other devices that hold the door or gate in a closed position.

Recommendation:
Adjust or replace door closer.
Barrier Priority:
Important (2): Should be completed as soon as possible. (Includes; Findings that would remove barriers to the greatest number of people to your goods and services)
Finding 849588 Main Photo
Image that depicts the citation requirements of the code or standard

Basement level: Jury Restroom

Finding: 7

The door is equipped with a door closer and returns to a closed position too quickly.

Door closers and gate closers shall be adjusted so that from an open position of 90 degrees, the time required to move the door to a position of 12 degrees from the latch is 5 seconds minimum.
Citation:
2010 ADAS Section 404.2.8.1
Door closers and gate closers shall be adjusted so that from an open position of 90 degrees, the time required to move the door to a position of 12 degrees from the latch is 5 seconds minimum.

Recommendation:
Adjust or replace door closer.
Barrier Priority:
Moderate (3): Should be completed as soon as possible, but there may be other items that will provide greater access to persons with disabilities. (Includes; Findings that have a high financial impact on the entity in relationship to the degree of access provided)
Finding 849576 Main Photo
Image that depicts the citation requirements of the code or standard
Additional Finding Photos
Finding 849576 Additional Photo

Finding: 8

The door exceeds the maximum allowable opening force.

Interior doors shall have a maximum opening force of 5 pounds.

These forces do not apply to the force required to retract latch bolts or disengage other devices that hold the door or gate in a closed position.
Citation:
2010 ADAS Section 404.2.9
Fire doors shall have a minimum opening force allowable by the appropriate administrative authority. The force for pushing or pulling open a door or gate other than fire doors shall be as follows: 1. Interior hinged doors and gates: 5 pounds (22.2 N) maximum. 2. Sliding or folding doors: 5 pounds (22.2 N) maximum. These forces do not apply to the force required to retract latch bolts or disengage other devices that hold the door or gate in a closed position.

Recommendation:
Adjust or replace door closers.
Barrier Priority:
Moderate (3): Should be completed as soon as possible, but there may be other items that will provide greater access to persons with disabilities. (Includes; Findings that have a high financial impact on the entity in relationship to the degree of access provided)
Finding 849577 Main Photo
Image that depicts the citation requirements of the code or standard
Additional Finding Photos
Finding 849577 Additional Photo

Finding: 9

The toilet paper is not installed within the compliant range.

Toilet paper dispensers shall be 7 inches minimum and 9 inches maximum in front of the water closet measured to the centerline of the dispenser. The outlet of the dispenser shall be 15 inches minimum and 48 inches maximum above the finish floor and shall not be located behind grab bars. Dispensers shall not be of a type that controls delivery or that does not allow continuous paper flow. There shall be a clearance of 1 1/2 inches minimum below the grab bar.
Citation:
2010 ADAS Section 604.7
Toilet paper dispensers shall comply with 309.4 and shall be 7 inches (180 mm) minimum and 9 inches (230 mm) maximum in front of the water closet measured to the centerline of the dispenser. The outlet of the dispenser shall be 15 inches (380 mm) minimum and 48 inches (1220 mm) maximum above the finish floor and shall not be located behind grab bars. Dispensers shall not be of a type that controls delivery or that does not allow continuous paper flow.

Recommendation:
Move dispenser to compliant range.
Barrier Priority:
Moderate (3): Should be completed as soon as possible, but there may be other items that will provide greater access to persons with disabilities. (Includes; Findings that have a high financial impact on the entity in relationship to the degree of access provided)
Finding 849578 Main Photo
Image that depicts the citation requirements of the code or standard

Finding: 10

The threshold is beveled with a slope greater than 1:2.

The threshold at a doorway shall be no higher than 1/2 inch. Changes in level between 1/4 inch and 1/2 inch must be beveled at 1:2 or less. 1/4 inch is the maximum vertical rise.
Citation:
2010 ADAS Section 404.2.5
Thresholds, if provided at doorways, shall be 1/2 inch (13 mm) high maximum. Raised thresholds and changes in level at doorways shall comply with 302 and 303.

Recommendation:
Reconfigure or replace with compliant threshold.
Barrier Priority:
Moderate (3): Should be completed as soon as possible, but there may be other items that will provide greater access to persons with disabilities. (Includes; Findings that have a high financial impact on the entity in relationship to the degree of access provided)
Finding 849580 Main Photo
Image that depicts the citation requirements of the code or standard

Basement level: Circulating Route

Finding: 11

The element projects more than 4 inches into the circulation path.

Wall-mounted objects that have leading edges between 27 inches and 80 inches from the floor must not project more than 4 inches into the circulation path. Protruding objects that extend to the floor or within 27 inches of the floor are cane detectable and are therefore not hazardous. Where it is necessary or desirable to have objects protrude from the wall, a manner of cane detection must be provided.
Citation:
2010 ADAS Section 307.2
Objects with leading edges more than 27 inches (685 mm) and not more than 80 inches (2030 mm) above the finish floor or ground shall protrude 4 inches (100 mm) maximum horizontally into the circulation path.

Recommendation:
Move cabinet to compliant location or place object below element for cane detection.
Barrier Priority:
Important (2): Should be completed as soon as possible. (Includes; Findings that would remove barriers to the greatest number of people to your goods and services)
Finding 849599 Main Photo
Image that depicts the citation requirements of the code or standard

Basement level: Men's restroom

Finding: 12

The door exceeds the maximum allowable opening force.

Interior doors shall have a maximum opening force of 5 pounds.

These forces do not apply to the force required to retract latch bolts or disengage other devices that hold the door or gate in a closed position.
Citation:
2010 ADAS Section 404.2.9
Fire doors shall have a minimum opening force allowable by the appropriate administrative authority. The force for pushing or pulling open a door or gate other than fire doors shall be as follows: 1. Interior hinged doors and gates: 5 pounds (22.2 N) maximum. 2. Sliding or folding doors: 5 pounds (22.2 N) maximum. These forces do not apply to the force required to retract latch bolts or disengage other devices that hold the door or gate in a closed position.

Recommendation:
Adjust or replace closer.
Barrier Priority:
Moderate (3): Should be completed as soon as possible, but there may be other items that will provide greater access to persons with disabilities. (Includes; Findings that have a high financial impact on the entity in relationship to the degree of access provided)
Finding 849593 Main Photo
Image that depicts the citation requirements of the code or standard

Finding: 13

The compartment door landing does not have 18 inches of strike side clearance.

Landings for compartment doors on the pull side must be as wide as the door plus an additional 18 inches on the strike side.
Citation:
2010 ADAS Section 404.2.4.1
Swinging doors and gates shall have maneuvering clearances complying with Table 404.2.4.1.

Recommendation:
Reconfigure restroom partition door.
Barrier Priority:
Moderate (3): Should be completed as soon as possible, but there may be other items that will provide greater access to persons with disabilities. (Includes; Findings that have a high financial impact on the entity in relationship to the degree of access provided)
Finding 849595 Main Photo
Image that depicts the citation requirements of the code or standard

Finding: 14

The toilet paper is not installed within the compliant range.

Toilet paper dispensers shall be 7 inches minimum and 9 inches maximum in front of the water closet measured to the centerline of the dispenser. The outlet of the dispenser shall be 15 inches minimum and 48 inches maximum above the finish floor and shall not be located behind grab bars. Dispensers shall not be of a type that controls delivery or that does not allow continuous paper flow. There shall be a clearance of 1 1/2 inches minimum below the grab bar.
Citation:
2010 ADAS Section 604.7
Toilet paper dispensers shall comply with 309.4 and shall be 7 inches (180 mm) minimum and 9 inches (230 mm) maximum in front of the water closet measured to the centerline of the dispenser. The outlet of the dispenser shall be 15 inches (380 mm) minimum and 48 inches (1220 mm) maximum above the finish floor and shall not be located behind grab bars. Dispensers shall not be of a type that controls delivery or that does not allow continuous paper flow.

Recommendation:
Move dispenser to compliant range.
Barrier Priority:
Moderate (3): Should be completed as soon as possible, but there may be other items that will provide greater access to persons with disabilities. (Includes; Findings that have a high financial impact on the entity in relationship to the degree of access provided)
Finding 849596 Main Photo
Image that depicts the citation requirements of the code or standard

Basement level: Women's restroom

Finding: 15

The compartment door landing does not have 18 inches of strike side clearance.

Landings for compartment doors on the pull side must be as wide as the door plus an additional 18 inches on the strike side.
Citation:
2010 ADAS Section 404.2.4.1
Swinging doors and gates shall have maneuvering clearances complying with Table 404.2.4.1.

Recommendation:
Reconfigure partition door.
Barrier Priority:
Moderate (3): Should be completed as soon as possible, but there may be other items that will provide greater access to persons with disabilities. (Includes; Findings that have a high financial impact on the entity in relationship to the degree of access provided)
Finding 849589 Main Photo
Image that depicts the citation requirements of the code or standard

Finding: 16

The force required to operate the element exceeds the maximum allowable force.

The force required to activate operable parts is 5 pounds maximum.
Citation:
2010 ADAS Section 309.4
Operable parts shall be operable with one hand and shall not require tight grasping, pinching, or twisting of the wrist. The force required to activate operable parts shall be 5 pounds (22.2 N) maximum.

Recommendation:
Adjust or replace valve control.
Barrier Priority:
Moderate (3): Should be completed as soon as possible, but there may be other items that will provide greater access to persons with disabilities. (Includes; Findings that have a high financial impact on the entity in relationship to the degree of access provided)
Finding 849590 Main Photo
Image that depicts the citation requirements of the code or standard

Finding: 17

The clear floor space around the toilet is obstructed by the (filing cabinet and toilet paper dispenser).

No fixtures are allowed in the clear floor space required for the toilet.

The required clearance around the water closet shall be permitted to overlap the water closet, associated grab bars, dispensers, sanitary napkin disposal units, coat hooks, shelves, accessible routes, clear floor space and clearances required at other fixtures, and the turning space. No other fixtures or obstructions shall be located within the required water closet clearance.
Citation:
2010 ADAS Section 604.3.2
The required clearance around the water closet shall be permitted to overlap the water closet, associated grab bars, dispensers, sanitary napkin disposal units, coat hooks, shelves, accessible routes, clear floor space and clearances required at other fixtures, and the turning space. No other fixtures or obstructions shall be located within the required water closet clearance.

Recommendation:
Remove obstructions from toilet clear space.
Barrier Priority:
Moderate (3): Should be completed as soon as possible, but there may be other items that will provide greater access to persons with disabilities. (Includes; Findings that have a high financial impact on the entity in relationship to the degree of access provided)
Finding 849591 Main Photo
Image that depicts the citation requirements of the code or standard
Additional Finding Photos
Finding 849591 Additional Photo

Finding: 18

The door exceeds the maximum allowable opening force.

Interior doors shall have a maximum opening force of 5 pounds.

These forces do not apply to the force required to retract latch bolts or disengage other devices that hold the door or gate in a closed position.
Citation:
2010 ADAS Section 404.2.9
Fire doors shall have a minimum opening force allowable by the appropriate administrative authority. The force for pushing or pulling open a door or gate other than fire doors shall be as follows: 1. Interior hinged doors and gates: 5 pounds (22.2 N) maximum. 2. Sliding or folding doors: 5 pounds (22.2 N) maximum. These forces do not apply to the force required to retract latch bolts or disengage other devices that hold the door or gate in a closed position.

Recommendation:
Adjust or replace door closer.
Barrier Priority:
Moderate (3): Should be completed as soon as possible, but there may be other items that will provide greater access to persons with disabilities. (Includes; Findings that have a high financial impact on the entity in relationship to the degree of access provided)
Finding 849594 Main Photo
Image that depicts the citation requirements of the code or standard

Basement level: Clerks Office

Finding: 19

The force required to operate the door hardware exceeds 5 pounds.

The force required to activate operable parts is 5 pounds maximum.
Citation:
2010 ADAS Section 309.4
Operable parts shall be operable with one hand and shall not require tight grasping, pinching, or twisting of the wrist. The force required to activate operable parts shall be 5 pounds (22.2 N) maximum.

Recommendation:
Adjust or replace push bar.
Barrier Priority:
Important (2): Should be completed as soon as possible. (Includes; Findings that would remove barriers to the greatest number of people to your goods and services)
Finding 849603 Main Photo

Finding: 20

The door exceeds the maximum allowable opening force.

Interior doors shall have a maximum opening force of 5 pounds.

These forces do not apply to the force required to retract latch bolts or disengage other devices that hold the door or gate in a closed position.
Citation:
2010 ADAS Section 404.2.9
Fire doors shall have a minimum opening force allowable by the appropriate administrative authority. The force for pushing or pulling open a door or gate other than fire doors shall be as follows: 1. Interior hinged doors and gates: 5 pounds (22.2 N) maximum. 2. Sliding or folding doors: 5 pounds (22.2 N) maximum. These forces do not apply to the force required to retract latch bolts or disengage other devices that hold the door or gate in a closed position.

Recommendation:
Adjust or replace door closer.
Barrier Priority:
Important (2): Should be completed as soon as possible. (Includes; Findings that would remove barriers to the greatest number of people to your goods and services)
Finding 849604 Main Photo
Image that depicts the citation requirements of the code or standard

Finding: 21

The carpet, rug, or mat is not secured in place.

If carpet or carpet tile is used on a ground or floor surface, then it shall be securely attached; have a firm cushion, pad or backing or no cushion or pad; and have a level loop, textured loop, level-cut pile or level-cut/uncut pile texture. The maximum pile height shall be 1/2 inch. Exposed edges of carpet shall be fastened to floor surfaces and have trim along the entire length of the exposed edge. Recessed doormats shall be adequately anchored to prevent interference with wheelchair traffic.
Citation:
2010 ADAS Section 302.2
Carpet or carpet tile shall be securely attached and shall have a firm cushion, pad, or backing or no cushion or pad. Carpet or carpet tile shall have a level loop, textured loop, level cut pile, or level cut/uncut pile texture. Pile height shall be 1/2 inch (13 mm) maximum. Exposed edges of carpet shall be fastened to floor surfaces and shall have trim on the entire length of the exposed edge. Carpet edge trim shall comply with 303.

Recommendation:
Install rug grippers or replace.
Barrier Priority:
Important (2): Should be completed as soon as possible. (Includes; Findings that would remove barriers to the greatest number of people to your goods and services)
Finding 849605 Main Photo
Image that depicts the citation requirements of the code or standard

Finding: 22

The door exceeds the maximum allowable opening force.

Interior doors shall have a maximum opening force of 5 pounds.

These forces do not apply to the force required to retract latch bolts or disengage other devices that hold the door or gate in a closed position.
Citation:
2010 ADAS Section 404.2.9
Fire doors shall have a minimum opening force allowable by the appropriate administrative authority. The force for pushing or pulling open a door or gate other than fire doors shall be as follows: 1. Interior hinged doors and gates: 5 pounds (22.2 N) maximum. 2. Sliding or folding doors: 5 pounds (22.2 N) maximum. These forces do not apply to the force required to retract latch bolts or disengage other devices that hold the door or gate in a closed position.

Recommendation:
Adjust or replace door closer.
Barrier Priority:
High (1): Should be completed immediately. (Includes; Findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Finding 849606 Main Photo
Image that depicts the citation requirements of the code or standard

Finding: 23

The force required to operate the door hardware exceeds 5 pounds.

The force required to activate operable parts is 5 pounds maximum.
Citation:
2010 ADAS Section 309.4
Operable parts shall be operable with one hand and shall not require tight grasping, pinching, or twisting of the wrist. The force required to activate operable parts shall be 5 pounds (22.2 N) maximum.

Recommendation:
Adjust or replace push bar.
Barrier Priority:
High (1): Should be completed immediately. (Includes; Findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Finding 849607 Main Photo

Finding: 24

The door is equipped with a door closer and returns to a closed position too quickly.

Door closers and gate closers shall be adjusted so that from an open position of 90 degrees, the time required to move the door to a position of 12 degrees from the latch is 5 seconds minimum.
Citation:
2010 ADAS Section 404.2.8.1
Door closers and gate closers shall be adjusted so that from an open position of 90 degrees, the time required to move the door to a position of 12 degrees from the latch is 5 seconds minimum.

Recommendation:
Adjust or replace door closer.
Barrier Priority:
High (1): Should be completed immediately. (Includes; Findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Finding 849608 Main Photo
Image that depicts the citation requirements of the code or standard

Basement level: Records office

Finding: 25

The knee clearance is not a minimum of 27 inches above the finished floor.

The knee clearance shall be 11 inches deep minimum at 9 inches above the finish floor or ground, and 8 inches deep minimum at 27 inches above the finish floor or ground and 30 inches wide minimum.

Between 9 inches and 27 inches above the finish floor or ground, the knee clearance shall be permitted to reduce at a rate of 1 inch in depth for each 6 inches in height.
Citation:
2010 ADAS Section 306.3.3
Where knee clearance is required under an element as part of a clear floor space, the knee clearance shall be 11 inches (280 mm) deep minimum at 9 inches (230 mm) above the finish floor or ground, and 8 inches (205 mm) deep minimum at 27 inches (685 mm) above the finish floor or ground.

Recommendation:
Reconfigure or replace with compliant work station.
Barrier Priority:
Low (4): Should be completed as soon as possible due to being a technical violation, but may not result in providing greater access to persons with disabilities. (Includes; Findings that are technically violations but provide a moderate to low increase in accessibility compared to the financial impact on the entity)
Finding 849601 Main Photo
Image that depicts the citation requirements of the code or standard

Basement level: Accessible holding Cell

Finding: 26

The required clear floor space is not wide enough.

The clear floor or ground space shall be 30 inches minimum by 48 inches minimum.
Citation:
2010 ADAS Section 305.3
The clear floor or ground space shall be 30 inches (760 mm) minimum by 48 inches (1220 mm) minimum

Recommendation:
Create compliant clear floor space adjacent to bench.
Barrier Priority:
Important (2): Should be completed as soon as possible. (Includes; Findings that would remove barriers to the greatest number of people to your goods and services)
Finding 849626 Main Photo
Image that depicts the citation requirements of the code or standard
Additional Finding Photos
Finding 849626 Additional Photo
Finding 849626 Additional Photo

Finding: 27

The threshold is beveled with a slope greater than 1:2.

The threshold at a doorway shall be no higher than 1/2 inch. Changes in level between 1/4 inch and 1/2 inch must be beveled at 1:2 or less. 1/4 inch is the maximum vertical rise.
Citation:
2010 ADAS Section 404.2.5
Thresholds, if provided at doorways, shall be 1/2 inch (13 mm) high maximum. Raised thresholds and changes in level at doorways shall comply with 302 and 303.

Recommendation:
Reconfigure or replace with compliant threshold.
Barrier Priority:
Important (2): Should be completed as soon as possible. (Includes; Findings that would remove barriers to the greatest number of people to your goods and services)
Finding 849627 Main Photo
Image that depicts the citation requirements of the code or standard

Ground level: Upper court room

Finding: 28

The door exceeds the maximum allowable opening force.

Interior doors shall have a maximum opening force of 5 pounds.

These forces do not apply to the force required to retract latch bolts or disengage other devices that hold the door or gate in a closed position.
Citation:
2010 ADAS Section 404.2.9
Fire doors shall have a minimum opening force allowable by the appropriate administrative authority. The force for pushing or pulling open a door or gate other than fire doors shall be as follows: 1. Interior hinged doors and gates: 5 pounds (22.2 N) maximum. 2. Sliding or folding doors: 5 pounds (22.2 N) maximum. These forces do not apply to the force required to retract latch bolts or disengage other devices that hold the door or gate in a closed position.

Recommendation:
Adjust or replace door closers.
Barrier Priority:
Important (2): Should be completed as soon as possible. (Includes; Findings that would remove barriers to the greatest number of people to your goods and services)
Finding 849609 Main Photo
Image that depicts the citation requirements of the code or standard

Finding: 29

The force required to operate the door hardware exceeds 5 pounds.

The force required to activate operable parts is 5 pounds maximum.
Citation:
2010 ADAS Section 309.4
Operable parts shall be operable with one hand and shall not require tight grasping, pinching, or twisting of the wrist. The force required to activate operable parts shall be 5 pounds (22.2 N) maximum.

Recommendation:
Adjust or replace push bars.
Barrier Priority:
Important (2): Should be completed as soon as possible. (Includes; Findings that would remove barriers to the greatest number of people to your goods and services)
Finding 849610 Main Photo

Ground level: Men's restroom

Finding: 30

The door exceeds the maximum allowable opening force.

Interior doors shall have a maximum opening force of 5 pounds.

These forces do not apply to the force required to retract latch bolts or disengage other devices that hold the door or gate in a closed position.
Citation:
2010 ADAS Section 404.2.9
Fire doors shall have a minimum opening force allowable by the appropriate administrative authority. The force for pushing or pulling open a door or gate other than fire doors shall be as follows: 1. Interior hinged doors and gates: 5 pounds (22.2 N) maximum. 2. Sliding or folding doors: 5 pounds (22.2 N) maximum. These forces do not apply to the force required to retract latch bolts or disengage other devices that hold the door or gate in a closed position.

Recommendation:
Adjust or replace door closer.
Barrier Priority:
Moderate (3): Should be completed as soon as possible, but there may be other items that will provide greater access to persons with disabilities. (Includes; Findings that have a high financial impact on the entity in relationship to the degree of access provided)
Finding 849612 Main Photo
Image that depicts the citation requirements of the code or standard

Finding: 31

The compartment door is not self closing.

The water closet compartment shall be equipped with a door that has an automatic-closing device.
Citation:
2010 ADAS Section 604.8.1.2
Toilet compartment doors, including door hardware, shall comply with 404 except that if the approach is to the latch side of the compartment door, clearance between the door side of the compartment and any obstruction shall be 42 inches (1065 mm) minimum. Doors shall be located in the front partition or in the side wall or partition farthest from the water closet. Where located in the front partition, the door opening shall be 4 inches (100 mm) maximum from the side wall or partition farthest from the water closet. Where located in the side wall or partition, the door opening shall be 4 inches (100 mm) maximum from the front partition. The door shall be self-closing. A door pull complying with 404.2.7 shall be placed on both sides of the door near the latch. Toilet compartment doors shall not swing into the minimum required compartment area.

Recommendation:
Repair or replace hardware so door self-closes.
Barrier Priority:
Moderate (3): Should be completed as soon as possible, but there may be other items that will provide greater access to persons with disabilities. (Includes; Findings that have a high financial impact on the entity in relationship to the degree of access provided)
Finding 849614 Main Photo
Image that depicts the citation requirements of the code or standard

Finding: 32

The toilet paper is not installed within the compliant range.

Toilet paper dispensers shall be 7 inches minimum and 9 inches maximum in front of the water closet measured to the centerline of the dispenser. The outlet of the dispenser shall be 15 inches minimum and 48 inches maximum above the finish floor and shall not be located behind grab bars. Dispensers shall not be of a type that controls delivery or that does not allow continuous paper flow. There shall be a clearance of 1 1/2 inches minimum below the grab bar.
Citation:
2010 ADAS Section 604.7
Toilet paper dispensers shall comply with 309.4 and shall be 7 inches (180 mm) minimum and 9 inches (230 mm) maximum in front of the water closet measured to the centerline of the dispenser. The outlet of the dispenser shall be 15 inches (380 mm) minimum and 48 inches (1220 mm) maximum above the finish floor and shall not be located behind grab bars. Dispensers shall not be of a type that controls delivery or that does not allow continuous paper flow.

Recommendation:
Move dispenser to compliant range.
Barrier Priority:
Moderate (3): Should be completed as soon as possible, but there may be other items that will provide greater access to persons with disabilities. (Includes; Findings that have a high financial impact on the entity in relationship to the degree of access provided)
Finding 849615 Main Photo
Image that depicts the citation requirements of the code or standard

Ground level: Women's restroom

Finding: 33

The door exceeds the maximum allowable opening force.

Interior doors shall have a maximum opening force of 5 pounds.

These forces do not apply to the force required to retract latch bolts or disengage other devices that hold the door or gate in a closed position.
Citation:
2010 ADAS Section 404.2.9
Fire doors shall have a minimum opening force allowable by the appropriate administrative authority. The force for pushing or pulling open a door or gate other than fire doors shall be as follows: 1. Interior hinged doors and gates: 5 pounds (22.2 N) maximum. 2. Sliding or folding doors: 5 pounds (22.2 N) maximum. These forces do not apply to the force required to retract latch bolts or disengage other devices that hold the door or gate in a closed position.

Recommendation:
Adjust or replace door closer.
Barrier Priority:
Moderate (3): Should be completed as soon as possible, but there may be other items that will provide greater access to persons with disabilities. (Includes; Findings that have a high financial impact on the entity in relationship to the degree of access provided)
Finding 849617 Main Photo
Image that depicts the citation requirements of the code or standard

Finding: 34

The clear floor space for the element is obstructed.

The clear floor or ground space shall be 30 inches minimum by 48 inches minimum and free of obstructions.
Citation:
2010 ADAS Section 305.3
The clear floor or ground space shall be 30 inches (760 mm) minimum by 48 inches (1220 mm) minimum

Recommendation:
Move dispenser to compliant location with clear floor space outside of door swing.
Barrier Priority:
Moderate (3): Should be completed as soon as possible, but there may be other items that will provide greater access to persons with disabilities. (Includes; Findings that have a high financial impact on the entity in relationship to the degree of access provided)
Finding 849618 Main Photo
Image that depicts the citation requirements of the code or standard
Additional Finding Photos
Finding 849618 Additional Photo

Finding: 35

The compartment door is not self closing.

The water closet compartment shall be equipped with a door that has an automatic-closing device.
Citation:
2010 ADAS Section 604.8.1.2
Toilet compartment doors, including door hardware, shall comply with 404 except that if the approach is to the latch side of the compartment door, clearance between the door side of the compartment and any obstruction shall be 42 inches (1065 mm) minimum. Doors shall be located in the front partition or in the side wall or partition farthest from the water closet. Where located in the front partition, the door opening shall be 4 inches (100 mm) maximum from the side wall or partition farthest from the water closet. Where located in the side wall or partition, the door opening shall be 4 inches (100 mm) maximum from the front partition. The door shall be self-closing. A door pull complying with 404.2.7 shall be placed on both sides of the door near the latch. Toilet compartment doors shall not swing into the minimum required compartment area.

Recommendation:
Repair or replace hardware so door self-closes.
Barrier Priority:
Moderate (3): Should be completed as soon as possible, but there may be other items that will provide greater access to persons with disabilities. (Includes; Findings that have a high financial impact on the entity in relationship to the degree of access provided)
Finding 849619 Main Photo
Image that depicts the citation requirements of the code or standard

Finding: 36

The lavatory's clear floor space is not a minimum 30 inches wide by 48 inches deep.

A 30 inch by 48 inch clear floor space positioned for a forward approach with knee and toe clearance shall be provided.
Citation:
2010 ADAS Section 606.2
A clear floor space complying with 305, positioned for a forward approach, and knee and toe clearance complying with 306 shall be provided.

Recommendation:
Relocate trash can to provide clear floor space for lavatories.
Barrier Priority:
Moderate (3): Should be completed as soon as possible, but there may be other items that will provide greater access to persons with disabilities. (Includes; Findings that have a high financial impact on the entity in relationship to the degree of access provided)
Finding 849620 Main Photo
Image that depicts the citation requirements of the code or standard
Additional Finding Photos
Finding 849620 Additional Photo

Finding: 37

The toilet paper is not installed within the compliant range.

Toilet paper dispensers shall be 7 inches minimum and 9 inches maximum in front of the water closet measured to the centerline of the dispenser. The outlet of the dispenser shall be 15 inches minimum and 48 inches maximum above the finish floor and shall not be located behind grab bars. Dispensers shall not be of a type that controls delivery or that does not allow continuous paper flow. There shall be a clearance of 1 1/2 inches minimum below the grab bar.
Citation:
2010 ADAS Section 604.7
Toilet paper dispensers shall comply with 309.4 and shall be 7 inches (180 mm) minimum and 9 inches (230 mm) maximum in front of the water closet measured to the centerline of the dispenser. The outlet of the dispenser shall be 15 inches (380 mm) minimum and 48 inches (1220 mm) maximum above the finish floor and shall not be located behind grab bars. Dispensers shall not be of a type that controls delivery or that does not allow continuous paper flow.

Recommendation:
Move dispenser to compliant range.
Barrier Priority:
Moderate (3): Should be completed as soon as possible, but there may be other items that will provide greater access to persons with disabilities. (Includes; Findings that have a high financial impact on the entity in relationship to the degree of access provided)
Finding 849621 Main Photo
Image that depicts the citation requirements of the code or standard

Ground level: Circulating path

Finding: 38

The (AED cabinet) is positioned too high for either a side or front approach.

Where a clear floor or ground space allows a parallel approach to an element and the side reach is unobstructed, the high side reach shall be 48 inches maximum and the low side reach shall be 15 inches minimum above the finish floor or ground.

Where a forward reach is unobstructed, the high forward reach shall be 48 inches maximum and the low forward reach shall be 15 inches minimum above the finish floor or ground.
Citation:
2010 ADAS Section 308.1
Reach ranges shall comply with 308.

Recommendation:
Move cabinet to compliant height.
Barrier Priority:
Low (4): Should be completed as soon as possible due to being a technical violation, but may not result in providing greater access to persons with disabilities. (Includes; Findings that are technically violations but provide a moderate to low increase in accessibility compared to the financial impact on the entity)
Finding 849613 Main Photo
Image that depicts the citation requirements of the code or standard

Finding: 39

The carpet, rug, or mat is not secured in place.

If carpet or carpet tile is used on a ground or floor surface, then it shall be securely attached; have a firm cushion, pad or backing or no cushion or pad; and have a level loop, textured loop, level-cut pile or level-cut/uncut pile texture. The maximum pile height shall be 1/2 inch. Exposed edges of carpet shall be fastened to floor surfaces and have trim along the entire length of the exposed edge. Recessed doormats shall be adequately anchored to prevent interference with wheelchair traffic.
Citation:
2010 ADAS Section 302.2
Carpet or carpet tile shall be securely attached and shall have a firm cushion, pad, or backing or no cushion or pad. Carpet or carpet tile shall have a level loop, textured loop, level cut pile, or level cut/uncut pile texture. Pile height shall be 1/2 inch (13 mm) maximum. Exposed edges of carpet shall be fastened to floor surfaces and shall have trim on the entire length of the exposed edge. Carpet edge trim shall comply with 303.

Recommendation:
Install rug grippers or replace.
Barrier Priority:
High (1): Should be completed immediately. (Includes; Findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Finding 849628 Main Photo
Image that depicts the citation requirements of the code or standard

Finding: 40

The counter surface is greater than 36 inches off the finished floor.

A portion of the counter surface that is 36 inches long minimum and 36 inches high maximum above the finish floor shall be provided.

Where the provided counter surface is less than 36 inches long, the entire counter surface shall be 36 inches high maximum above the finish floor.
Citation:
2010 ADAS Section 904.4.1
A portion of the counter surface that is 36 inches (915 mm) long minimum and 36 inches (915 mm) high maximum above the finish floor shall be provided. A clear floor or ground space complying with 305 shall be positioned for a parallel approach adjacent to the 36 inch (915 mm) minimum length of counter.

Recommendation:
Rebuild or reconfigure counter to compliant height. Capital investment.
Barrier Priority:
Low (4): Should be completed as soon as possible due to being a technical violation, but may not result in providing greater access to persons with disabilities. (Includes; Findings that are technically violations but provide a moderate to low increase in accessibility compared to the financial impact on the entity)
Finding 849629 Main Photo
Image that depicts the citation requirements of the code or standard
Additional Finding Photos
Finding 849629 Additional Photo

Finding: 41

The force required to operate the door hardware exceeds 5 pounds.

The force required to activate operable parts is 5 pounds maximum.
Citation:
2010 ADAS Section 309.4
Operable parts shall be operable with one hand and shall not require tight grasping, pinching, or twisting of the wrist. The force required to activate operable parts shall be 5 pounds (22.2 N) maximum.

Recommendation:
Adjust or replace push bar.
Barrier Priority:
High (1): Should be completed immediately. (Includes; Findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Finding 849630 Main Photo

Finding: 42

The door is equipped with a door closer and returns to a closed position too quickly.

Door closers and gate closers shall be adjusted so that from an open position of 90 degrees, the time required to move the door to a position of 12 degrees from the latch is 5 seconds minimum.
Citation:
2010 ADAS Section 404.2.8.1
Door closers and gate closers shall be adjusted so that from an open position of 90 degrees, the time required to move the door to a position of 12 degrees from the latch is 5 seconds minimum.

Recommendation:
Adjust or replace door closers.
Barrier Priority:
High (1): Should be completed immediately. (Includes; Findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Finding 849631 Main Photo
Image that depicts the citation requirements of the code or standard

Ground level: Elevator

Finding: 43

The elevator audible signal is missing.

A visible and audible signal shall be provided at each hoistway entrance to indicate which car is answering a call and the car’s direction of travel. Where in-car signals are provided, they shall be visible from the floor area adjacent to the hall call buttons.

Audible signals shall sound once for the "up" direction and twice for the "down" direction or shall have verbal annunciators that say "up" or "down."
Citation:
2010 ADAS Section 407.2.2.2
Visible signal fixtures shall be centered at 72 inches (1830 mm) minimum above the finish floor or ground. The visible signal elements shall be 2 1/2 inches (64 mm) minimum measured along the vertical centerline of the element. Signals shall be visible from the floor area adjacent to the hall call button.

Recommendation:
Install compliant audible signal.
Barrier Priority:
Low (4): Should be completed as soon as possible due to being a technical violation, but may not result in providing greater access to persons with disabilities. (Includes; Findings that are technically violations but provide a moderate to low increase in accessibility compared to the financial impact on the entity)
Finding 849624 Main Photo
Image that depicts the citation requirements of the code or standard

Finding: 44

The elevator in car audible car position indicator signal is missing.

Audible and visible car position indicators shall be provided in elevator cars.
Citation:
2010 ADAS Section 407.4.8
Audible and visible car position indicators shall be provided in elevator cars.

Recommendation:
Install audible position indicator.
Barrier Priority:
Low (4): Should be completed as soon as possible due to being a technical violation, but may not result in providing greater access to persons with disabilities. (Includes; Findings that are technically violations but provide a moderate to low increase in accessibility compared to the financial impact on the entity)
Finding 849625 Main Photo
Image that depicts the citation requirements of the code or standard

Parking: Accessible Spaces (lot)

Finding: 45

The access aisle contains abrupt edges and surface irregularities over a 1/4 inches.

Parking spaces and access aisles serving them shall be stable, firm, and slip resistant. Access aisles shall be at the same level as the parking spaces they serve. Changes in level are not permitted and shall not be sloped steeper than 2% in any direction.
Citation:
2010 ADAS Section 502.4
Parking spaces and access aisles serving them shall comply with 302. Access aisles shall be at the same level as the parking spaces they serve. Changes in level are not permitted.

Recommendation:
Repave and repaint.
Barrier Priority:
Low (4): Should be completed as soon as possible due to being a technical violation, but may not result in providing greater access to persons with disabilities. (Includes; Findings that are technically violations but provide a moderate to low increase in accessibility compared to the financial impact on the entity)
Finding 849643 Main Photo
Image that depicts the citation requirements of the code or standard

Finding: 46

The cross slope (short dimension) of the access aisle exceeds 2%.

The cross slope in an accessible parking stall and the access aisle must not exceed 2%.
Citation:
2010 ADAS Section 502.4
Parking spaces and access aisles serving them shall comply with 302. Access aisles shall be at the same level as the parking spaces they serve. Changes in level are not permitted.

Recommendation:
Repave and repaint.
Barrier Priority:
Low (4): Should be completed as soon as possible due to being a technical violation, but may not result in providing greater access to persons with disabilities. (Includes; Findings that are technically violations but provide a moderate to low increase in accessibility compared to the financial impact on the entity)
Finding 849644 Main Photo
Image that depicts the citation requirements of the code or standard

Finding: 47

The running slope of the access aisle (long dimension) exceeds 2%.

The running slope in an accessible parking stall and the access aisle must not exceed 2%.
Citation:
2010 ADAS Section 502.4
Parking spaces and access aisles serving them shall comply with 302. Access aisles shall be at the same level as the parking spaces they serve. Changes in level are not permitted.

Recommendation:
Repave and repaint.
Barrier Priority:
Low (4): Should be completed as soon as possible due to being a technical violation, but may not result in providing greater access to persons with disabilities. (Includes; Findings that are technically violations but provide a moderate to low increase in accessibility compared to the financial impact on the entity)
Finding 849645 Main Photo
Image that depicts the citation requirements of the code or standard

Finding: 48

The running slope (long dimension) of the accessible parking stall exceeds 2%.

The running slope in an accessible parking stall and the access aisle must not exceed 2%.
Citation:
2010 ADAS Section 502.4
Parking spaces and access aisles serving them shall comply with 302. Access aisles shall be at the same level as the parking spaces they serve. Changes in level are not permitted.

Recommendation:
Repave and repaint.
Barrier Priority:
Low (4): Should be completed as soon as possible due to being a technical violation, but may not result in providing greater access to persons with disabilities. (Includes; Findings that are technically violations but provide a moderate to low increase in accessibility compared to the financial impact on the entity)
Finding 849646 Main Photo
Image that depicts the citation requirements of the code or standard

Finding: 49

The cross slope (narrow dimension) of the parking stall exceeds 2%.

The running and cross slope in an accessible parking stall and the access aisle must not exceed 2%.
Citation:
2010 ADAS Section 502.4
Parking spaces and access aisles serving them shall comply with 302. Access aisles shall be at the same level as the parking spaces they serve. Changes in level are not permitted.

Recommendation:
Repave and repaint.
Barrier Priority:
Low (4): Should be completed as soon as possible due to being a technical violation, but may not result in providing greater access to persons with disabilities. (Includes; Findings that are technically violations but provide a moderate to low increase in accessibility compared to the financial impact on the entity)
Finding 849647 Main Photo
Image that depicts the citation requirements of the code or standard

Finding: 50

The parking stall contains abrupt edges and surface irregularities over a 1/4 inch vertical.

Parking spaces and access aisles serving them shall be stable, firm, and slip resistant. Access aisles shall be at the same level as the parking spaces they serve. Changes in level are not permitted and shall not be sloped steeper than 2% in any direction.
Citation:
2010 ADAS Section 502.4
Parking spaces and access aisles serving them shall comply with 302. Access aisles shall be at the same level as the parking spaces they serve. Changes in level are not permitted.

Recommendation:
Repave and repaint.
Barrier Priority:
Low (4): Should be completed as soon as possible due to being a technical violation, but may not result in providing greater access to persons with disabilities. (Includes; Findings that are technically violations but provide a moderate to low increase in accessibility compared to the financial impact on the entity)
Finding 849648 Main Photo
Image that depicts the citation requirements of the code or standard
Additional Finding Photos
Finding 849648 Additional Photo

Parking: Accessible route (Front)

Finding: 51

The ramp on the accessible route has cross slopes greater than 2%.

Surface cross slopes shall not exceed one unit vertical in 48 units horizontal (2-percent slope).
Citation:
2010 ADAS Section 405.3
Cross slope of ramp runs shall not be steeper than 1:48.

Recommendation:
Reconfigure ramp to compliant slope. Capital investment.
Barrier Priority:
Important (2): Should be completed as soon as possible. (Includes; Findings that would remove barriers to the greatest number of people to your goods and services)
Finding 849632 Main Photo
Image that depicts the citation requirements of the code or standard

Finding: 52

There is a change in level greater than 1/4 inch.

1/4 inch is the maximum vertical rise. Changes in level between 1/4 inch and 1/2 inch must be beveled at 1:2 or less. Changes in level greater than 1/2 inch must be by way of a ramp.
Citation:
2010 ADAS Section 303.3
Changes in level between 1/4 inch (6.4 mm) high minimum and 1/2 inch (13 mm) high maximum shall be beveled with a slope not steeper than 1:2.

Recommendation:
Cut VHD to eliminate trip hazard.
Barrier Priority:
Important (2): Should be completed as soon as possible. (Includes; Findings that would remove barriers to the greatest number of people to your goods and services)
Finding 849633 Main Photo
Image that depicts the citation requirements of the code or standard

Finding: 53

The ramp does not meet minimum width requirements.

Ramps shall have a minimum clear width of 36 inches
Citation:
2010 ADAS Section 405.5
The clear width of a ramp run and, where handrails are provided, the clear width between handrails shall be 36 inches (915 mm) minimum.

Recommendation:
Reconfigure ramp to compliant width. Capital investment.
Barrier Priority:
Important (2): Should be completed as soon as possible. (Includes; Findings that would remove barriers to the greatest number of people to your goods and services)
Finding 849634 Main Photo
Image that depicts the citation requirements of the code or standard

Finding: 54

The landing at the bottom of the ramp has a slope greater than 2%.

Bottom landings shall have a dimension in the direction of ramp run of not less than 60 inches and have a slope of 2% maximum in any direction.
Citation:
2010 ADAS Section 405.7.1
Landings shall comply with 302. Changes in level are not permitted.

2010 ADAS Section 405.7.1 Exception
Slopes not steeper than 1:48 shall be permitted.

Recommendation:
Raise/level landing to compliant slope. Capital investment.
Barrier Priority:
Important (2): Should be completed as soon as possible. (Includes; Findings that would remove barriers to the greatest number of people to your goods and services)
Finding 849635 Main Photo
Image that depicts the citation requirements of the code or standard

Finding: 55

The landing at the change of direction does not meet minimum size requirements.

Landings at a change of direction shall have a dimension of not less than 60 inches by 60 inches.
Citation:
2010 ADAS Section 405.7.4
Ramps that change direction between runs at landings shall have a clear landing 60 inches (1525 mm) minimum by 60 inches (1525 mm) minimum.

Recommendation:
Reconfigure ramp to compliant size. Capital investment.
Barrier Priority:
Important (2): Should be completed as soon as possible. (Includes; Findings that would remove barriers to the greatest number of people to your goods and services)
Finding 849636 Main Photo
Image that depicts the citation requirements of the code or standard
Additional Finding Photos
Finding 849636 Additional Photo

Finding: 56

The width between handrails is less than 36 inches.

The clear width of a ramp run where handrails are provided, shall be 36 inches minimum.
Citation:
2010 ADAS Section 405.5
The clear width of a ramp run and, where handrails are provided, the clear width between handrails shall be 36 inches (915 mm) minimum.

Recommendation:
Reconfigure ramp to compliant width. Capital investment.
Barrier Priority:
Important (2): Should be completed as soon as possible. (Includes; Findings that would remove barriers to the greatest number of people to your goods and services)
Finding 849637 Main Photo

Finding: 57

The handrail does not extend past the ramp.

Handrails must be between 34 inches and 38 inches above the ramp surface and must extend beyond the top and bottom of the ramp run 12 inches horizontally. The 12 inches horizontal extensions must not include the radius at the top end of round handrails. Extensions shall return to a wall, guard, or the landing surface, or shall be continuous to the handrail of an adjacent ramp run.
Citation:
2010 ADAS Section 505.10.1
Ramp handrails shall extend horizontally above the landing for 12 inches (305 mm) minimum beyond the top and bottom of ramp runs. Extensions shall return to a wall, guard, or the landing surface, or shall be continuous to the handrail of an adjacent ramp run.

Recommendation:
Install handrail extensions.
Barrier Priority:
Important (2): Should be completed as soon as possible. (Includes; Findings that would remove barriers to the greatest number of people to your goods and services)
Finding 849638 Main Photo
Image that depicts the citation requirements of the code or standard
Additional Finding Photos
Finding 849638 Additional Photo

Finding: 58

The handrail extension is not a minimum 12 inches.

Handrails must be between 34 inches and 38 inches above the ramp surface and must extend beyond the top and bottom of the ramp run 12 inches horizontally. The 12 inches horizontal extensions must not include the radius at the top end of round handrails. Extensions shall return to a wall, guard, or the landing surface, or shall be continuous to the handrail of an adjacent ramp run.
Citation:
2010 ADAS Section 505.10.1
Ramp handrails shall extend horizontally above the landing for 12 inches (305 mm) minimum beyond the top and bottom of ramp runs. Extensions shall return to a wall, guard, or the landing surface, or shall be continuous to the handrail of an adjacent ramp run.

Recommendation:
Extend handrailing.
Barrier Priority:
Important (2): Should be completed as soon as possible. (Includes; Findings that would remove barriers to the greatest number of people to your goods and services)
Finding 849639 Main Photo
Image that depicts the citation requirements of the code or standard

Finding: 59

The path of contains multiple issues and is not accessible.

The path of travel exceeds the maximum allowable cross and running slope requirements. It also contains changes in level and/or gaps that exceed the allowable maximum requirements.
Citation:
2010 ADAS Section 403.1
Walking surfaces that are a part of an accessible route shall comply with 403.

Recommendation:
Remediate, remove VHDs, repave and/or reconfigure accessible path. Capital investment.
Barrier Priority:
Important (2): Should be completed as soon as possible. (Includes; Findings that would remove barriers to the greatest number of people to your goods and services)
Finding 849640 Main Photo
Additional Finding Photos
Finding 849640 Additional Photo
Finding 849640 Additional Photo
Finding 849640 Additional Photo
Finding 849640 Additional Photo

Finding: 60

The curb ramp on the accessible route has cross slopes greater than 2%.

Surface cross slopes shall not exceed one unit vertical in 48 units horizontal (2-percent slope).
Citation:
2010 ADAS Section 405.3
Cross slope of ramp runs shall not be steeper than 1:48.

2010 ADAS Section 406.1
Curb ramps on accessible routes shall comply with 406, 405.2 through 405.5, and 405.10.

Recommendation:
Repour ramp to compliant slope.
Barrier Priority:
Important (2): Should be completed as soon as possible. (Includes; Findings that would remove barriers to the greatest number of people to your goods and services)
Finding 849641 Main Photo
Image that depicts the citation requirements of the code or standard

Finding: 61

There is a change in level greater than 1/4 inch.

1/4 inch is the maximum vertical rise. Changes in level between 1/4 inch and 1/2 inch must be beveled at 1:2 or less. Changes in level greater than 1/2 inch must be by way of a ramp.
Citation:
2010 ADAS Section 303.3
Changes in level between 1/4 inch (6.4 mm) high minimum and 1/2 inch (13 mm) high maximum shall be beveled with a slope not steeper than 1:2.

Recommendation:
Cut VHD to remove trip hazard.
Barrier Priority:
Important (2): Should be completed as soon as possible. (Includes; Findings that would remove barriers to the greatest number of people to your goods and services)
Finding 849642 Main Photo
Image that depicts the citation requirements of the code or standard

Parking: Accessible route (side)

Finding: 62

The ramps exceeds the maximum running slope (direction of travel) allowable of 8.33%.

Ramps should have the least possible slope but in no case more than 8.3% (1:12).
Citation:
2010 ADAS Section 405.2
Ramp runs shall have a running slope not steeper than 1:12.

Recommendation:
N/A - Refer to Finding
Barrier Priority:
N/A
Finding 849649 Main Photo
Image that depicts the citation requirements of the code or standard

Finding: 63

The ramp on the accessible route has cross slopes greater than 2%.

Surface cross slopes shall not exceed one unit vertical in 48 units horizontal (2-percent slope).
Citation:
2010 ADAS Section 405.3
Cross slope of ramp runs shall not be steeper than 1:48.

Recommendation:
N/A - Refer to Finding
Barrier Priority:
N/A
Finding 849650 Main Photo
Image that depicts the citation requirements of the code or standard

Finding: 64

The landing at the bottom of the ramp has a slope greater than 2%.

Bottom landings shall have a dimension in the direction of ramp run of not less than 60 inches and have a slope of 2% maximum in any direction.
Citation:
2010 ADAS Section 405.7.1
Landings shall comply with 302. Changes in level are not permitted.

2010 ADAS Section 405.7.1 Exception
Slopes not steeper than 1:48 shall be permitted.

Recommendation:
N/A - Refer to Finding
Barrier Priority:
N/A
Finding 849651 Main Photo
Image that depicts the citation requirements of the code or standard

Finding: 65

The handrail is not continuous the entire length of the ramp.

The handrail must be continuous. Handrails shall be placed on each side of each ramp, and shall be continuous the full length of the ramp. The inside handrail on switchback or dogleg ramps shall always be continuous.
Citation:
2010 ADAS Section 505.3
Handrails shall be continuous within the full length of each stair flight or ramp run. Inside handrails on switchback or dogleg stairs and ramps shall be continuous between flights or runs.

Recommendation:
N/A - Refer to Finding
Barrier Priority:
N/A
Finding 849652 Main Photo
Additional Finding Photos
Finding 849652 Additional Photo

Finding: 66

The handrail is obstructed along the bottom of the gripping surface.

The bottom of handrail gripping surfaces shall not be obstructed for more than 20 percent of their length.
Citation:
2010 ADAS Section 505.6
Handrail gripping surfaces shall be continuous along their length and shall not be obstructed along their tops or sides. The bottoms of handrail gripping surfaces shall not be obstructed for more than 20 percent of their length. Where provided, horizontal projections shall occur 1 1/2 inches (38 mm) minimum below the bottom of the handrail gripping surface.

Recommendation:
N/A - Refer to Finding
Barrier Priority:
N/A
Finding 849653 Main Photo

Finding: 67

The handrail does not extend past the ramp.

Handrails must be between 34 inches and 38 inches above the ramp surface and must extend beyond the top and bottom of the ramp run 12 inches horizontally. The 12 inches horizontal extensions must not include the radius at the top end of round handrails. Extensions shall return to a wall, guard, or the landing surface, or shall be continuous to the handrail of an adjacent ramp run.
Citation:
2010 ADAS Section 505.10.1
Ramp handrails shall extend horizontally above the landing for 12 inches (305 mm) minimum beyond the top and bottom of ramp runs. Extensions shall return to a wall, guard, or the landing surface, or shall be continuous to the handrail of an adjacent ramp run.

Recommendation:
N/A - Refer to Finding
Barrier Priority:
N/A
Finding 849654 Main Photo
Image that depicts the citation requirements of the code or standard
Additional Finding Photos
Finding 849654 Additional Photo

Finding: 68

The path of contains multiple issues and is not accessible.

The path of travel exceeds the maximum allowable cross and running slope requirements. It also contains changes in level and/or gaps that exceed the allowable maximum requirements.
Citation:
2010 ADAS Section 403.1
Walking surfaces that are a part of an accessible route shall comply with 403.

Recommendation:
N/A - Refer to Finding
Barrier Priority:
N/A
Finding 849655 Main Photo
Additional Finding Photos
Finding 849655 Additional Photo
Finding 849655 Additional Photo